Proteção Anti-Ilhamento da Geração Distribuída: análise da atuação indevida da função de subtensão devido a curtos-circuitos em alimentadores adjacentes

  • Jamenson Guilherme Ozelame Creluz – Cooperativa de Distribuição de Energia, Universidade Federal de Santa Maria - UFSM
  • Adriano Peres de Morais Universidade Federal de Santa Maria - UFSM
  • Adriano Marchesan Instituto Federal Farroupilha - IFF
  • João Paulo Abreu Vieira Universidade Federal do Pará - UFPA
Keywords: Distributed generation, Anti-islanding protection, Undervoltage function

Abstract

The significant growth in the number of connections of distributed generation (DG) units in distribution networks increases the operational complexity of such networks. One of the complicating factors is the improper action of the DG protection against islanding using an undervoltage relay in the event of short-circuits in feeders adjacent to the generation connection. In this sense, this study investigates through computer simulation in which situations this undue actuation occurs and which circuit elements influence the occurrence or not of these actuations.